Description
Measuring instrument of a high voltage of direct and alternating current RD-140

Purpose of the RD-140 measuring instrument

It is intended for measurement of alternating sinusoidal voltage with a frequency of 50... 60 Hz to 100 kV and constant tension to 140 kV.

RD-140 provides measurement with high precision

  • the operating value of an alternating voltage with a frequency of 50 Hz, kV;
  • average value of constant tension, kV;

RD-140 can be used in testing high-voltage laboratories of an electrotechnical and power profile, and also research establishments.

Technical characteristics of the RD-140 measuring instrument

Characteristic Value
Range of voltage measurements of a direct current, kV 10... 140
Range of voltage measurements of alternating current (the operating value), kV 10... 100
Range of frequencies at voltage measurement of alternating current, Hz 47,5... 52,5
Entrance resistance of the high-voltage RD140-BV block on a direct current, megohm 1600
Entrance resistance of the high-voltage RD140-BV block on alternating current with a frequency of 50 Hz, megohm, not less 200
Limits of the allowed relative error at measurement of tension of a direct current, % ±0,9
Limits of the allowed relative error at measurement of tension of alternating current, % ±0,7
Food of BV and MI is made from the built-in Ni-MH of accumulators of the AA size of 1,2 V and with a capacity of 1,8 Ach
supply voltage, In 5±0,2
duration of continuous work without recharge, h, not less 8
Range of action of a radio channel, m, not less 5
Duration of continuous work of RD-140 at the maximum entrance tension, hour, no more 1
Duration of continuous work of RD-140 at an entrance tension to 75 kV, hour, no more 8
Time of establishment of an operating mode after inclusion of food, min. 1
Overall dimensions, mm:
RD140-BV Ø280 x 880
RD140-MI 95 x 190 x 40
Weight, kg, no more:
RD140-BV 11
RD140-MI 0,5
Service life, years, not less 10
Contact the seller
Measuring instrument of a high voltage of direct and alternating current RD-140
Measuring instrument of a high voltage of direct and alternating current RD-140
for
by the goods
Your message must contain at least 20 symbols. The message must not be more than 2000 symbols.
Obligatory field is not filled
The field is wrongly filled
The field is wrongly filled
Shipping method
Compare0
ClearSelected items: 0