Installation proboyny universal UPU - 10 is intended for test of isolation of the electrotechnical equipment and materials by the variable sinusoidalnymnapryazheniye with a frequency of 50 Hz and the straightened tension of negative polarity regulated within 0 - 10 kV with output current to 100 ma
Scope – the electrician and the power engineering specialist.
Thanks to the raised output current installation can be used for test on an alternating voltage of isolation of windings of large electrical machines. With success it can be used for test of protective equipment for the corresponding tension (gloves, etc. ), and also for a charge of capacitor stores of energy.
1.2 Installation is calculated for operation in rooms or under a canopy at working values of air temperature from plus 5 °C to plus 40 °C, relative humidity to 80% at a temperature plus 20 °C and the atmospheric pressure of 84,0 - 106,7 kPa (630 – 800 mm Hg).
1.3 Food – a single - phase network of sinusoidal alternating current of 220±20 V, with a frequency of 50±1 Hz.
1.4 Installation is served by one operator with the right of work on installations with tension higher than 1000B.
2. SPECIFICATIONS
2.1 Limits of installation of output tension, kV, 1; 3; 10
2.2 The given relative error of installation and measurement of day off
tension, % , no more, - 3
2.3 The maximum output current, ma, - 100
2.4 The given relative error of measurement of current, % , no more - 3
2.5 A threshold of operation of current protection, ma, - 102±2
2.6 Power consumption, V. A, no more than 1000
2.7 Overall dimensions, mm, the control unit - 320х200х355 block of a high voltage - 315х290х410
2.8. Weight, kg, no more:
the control unit - 15
the block of a high voltage - 25
2.9. Operating time in the continuous mode at the maximum power, hour, - 8
2.10. Average service life of a product, years – 6
NOTE. The kilovoltmeter of installation measures on an alternating voltage - the operating value, on straightened – amplitude value of tension.
The milliamperemeter on alternating current measures the operating value, on straightened
average (srednevypryamlenny) value of current.