Folding measuring transformers of current SACI/SASI in the plastic case, the TA100P series
- 8.96 EUR/pcs - from 100 pcs
- Customer pickup,
- Courier
- In detail
- BrandSACI
- Country of manufactureSpain
- серияTA100P
Folding transformers of current of production SACI of the TA100P series have the demountable core which provides expeditious installation on the tire or on a cable without rupture of a chain, i. e. it is possible just "to throw" the conductor that allows to latch the current transformer on the tire or a cable without labor - consuming dismantling of the busline at the expense of what installation time in comparison with ordinary transformers of current TA100P is reduced several times.
Transformers of current TA100P are manufactured of high - quality materials. Connecting plugs of a secondary winding are made of the nickelized brass, on each plug is available about two screws (double plugs) that allows to replace easily devices or to carry out other operations on a secondary winding, without disconnecting a chain.
The case made of the self - fading plastic possesses fine resistance to mechanical and thermal loadings. Magnetic plates with the focused Fe - SI grains of the alloy characterizing by high permeability are specially recommended by the manufacturer of plates for transformers of current of this type.
Folding transformers of current TA100P are manufactured of plastic. Cases for transformers of current TA100P stamp serially and a certain quantity in a warehouse at SACI plant practically is always available. Therefore terms of production of transformers small also make 1 - 2 weeks in the presence of all accessories of plastic. The weight of folding transformers of current from plastic is much less, than at current transformers from pitch that it is important to consider when transporting and calculating logistic expenses.
Technical characteristics of the folding measuring transformer of current (plastic case) of TA100P
TA100P model
Size of the tire (mm) 100×80
Diameter of a cable (mm) Ø 80
Class of accuracy 0,5 1 3
Current on primary winding (A) of VA
250 2,5 3,75
300 3,75 5
400 2,5 3,75 7,5
500 3,75 5 15
600 5 7,5 20
750 7,5 10 20
800 7,5 10 20
1000 10 15 20
1200 15 20 30
1500 15 20 30
2000 20 30 45