Fire-resistant (N)HXH FE180/E90 to buy a cable in Ukraine-best the price!
NHXHFE180/E30 cable: application
Are used by Kabel in those areas where in connection with high concentration of property in case of fire it is necessary to minimize human and material losses, e.g., in plants, the municipal equipment, hotels, the airports, the railroads, hospitals and policlinics (DINVDE0107), department stores, rooms allocated for electronic information processing, theaters, movie theaters, high-rise buildings in places of a mass congestion of people, schools, etc. (DINVDE0108), in the mining industry, on sea drilling rigs, the equipment intended for traffic adjustment in installations of emergency power supply and systems of the alarm system.
The cable is intended for the fixed conducting in dry, damp and very damp rooms outside, in plaster and under plaster, and also for conducting in concrete and in a stone laying. This cable can be also laid in pipes in the open air or in the earth. Besides, the DINVDE0298 standards part 1 and 2 are valid. Also laying in a pipe is admissible if it is possible to provide lack of water in it. FE180: Safety of isolation within 180 minutes. Part 814 = IEC60331 are tested according to DINVDE0472. Safety of isolation at direct influence of a flame, time of test of 180 minutes. E30: Preservation of operability of electric cable networks not less than 30 minutes, compliance to standards of fire safety (appendix 1 to DINVDE0108 part 1).
NHXH FE180/E30 cable: Technical characteristics:
the cable which is not containing halogens DINVDE0266 agrees with the improved characteristics of fire safety
Safety of isolation within 180 minutes DINVDE0472 part 814 agrees
Preservation of working capacity within 30 minutes agrees DINVDE4102 part 12
Temperature range -30 °sdo + 70 °C
admissible production temperature on a cable +90 °C
Rated voltage of U0/U0,6/1 of kV
Test voltage is 4000 V
Minimum radius of a bend about 15 hkabel D
Resistance to radiation to 200 x106 of kJ/kg (to 200 Mrad)
Structure of the NHXH FE180/E30 cable
naked copper conductors, odnoil multiwire, correspond to DINVDE0295 of C. 1 or C. 2, BS6360 C. 1 or 2, IEC60228 of C. 1 or 2, HD383
double isolation of veins:
mica tape and the sewed polymer according to DINVDE0207 part 23 HI1
Color of veins corresponds to DINVDE0293
Protective wire greenish-yellow, from 3 veins
veins are twisted together
the bandage protecting from a flame from fiber glass
the external cover orange, the polyolefin mix corresponding to DINVDE0207 part 24 HM4 does not ignite