E-2,5-0,9GM boiler (fuel oil, diesel, oven fuel)
- Customer pickup,
- Courier
- In detail
(View map)
- Country of manufactureUkraine
- Boiler typeSteam
- Rated power1800 kW
- Weight8100 g
- Constructive featureWater-tube
- Coefficient of performance (COP)87 %
- PressureLow pressure
- Расход топлива
- мазут (дизель, печное топливо)190 кг/ч
PJSC Monastyrishchensky Engineering Plant offers the services to your enterprise for production and delivery of E-2,5-0,9 boilers of hypermarket (fuel fuel oil, the diesel, oven fuel). Delivery of boilers is made by the uniform transportable block in assembled form in a brickwork envelope and a covering.
Boilers of E-2,5-0,9GM belong to type of vertically water pipe two-drum coppers with natural circulation and is intended for production of saturated steam by working pressure to 0,8mpa, used in the industry and agriculture for technological, economic and domestic needs. The copper is calculated for work on natural gas and on fuel oil. The design of pipe system of a copper maintains short-term increase in pressure in a fire chamber to 3000 Pas and depression in a fire chamber to 400 Pas. On stability and influence of temperature and humidity of air boilers are manufactured in climatic modification of UHL, category of placement 4 in accordance with GOST 15150-69.
The design of coppers provides their installation in areas with seismicity to 6 points on MSK-64 scale.
(Fuel fuel oil, the diesel, oven fuel) enters a set of delivery of the E-2,5-0,9GM boiler:
- system of automatic control and safety of "Alpha M",
- gorelochny device
- DN-6,3 smoke exhauster,
- fan,
- nutritious pump "Lowara",
- shutoff valves and devices of control within a copper,
- a ladder with the platform, etc.
Name |
Fuel |
|
gas |
fuel oil |
|
Steam generating capacity, t/h, not less |
2,5 |
2,5 |
Absolute vapor pressure, MPa (kgf/cm2) |
0,9(9) |
0,9(9) |
Settlement temperature of feedwater, °C |
50±10 |
50±10 |
Calorific ability of fuel, MDzh/m3; MDzh/kg |
37,1 |
40,3 |
Fuel consumption at a rated load, kg/h (nm3/h), no more |
210 |
190 |
Efficiency, %, not less |
89 |
87 |
The established electric power, kW, no more |
12 |
12 |
Dimensions of a copper, mm, no more length |
5845 3230 |
5845 3230 |
height |
2700 |
2700 |
Mass of a copper, kg, no more |
8100 |
8100 |
Gas pressure before a torch on a rated load, kPa |
2,8 |
--- |
Gas pressure in front of the block of valves, kPa |
6,9 – 7,0 |
--- |
Pressure of liquid fuel on a rated load, kPa |
--- |
86,0 |
Air pressure before a torch on a rated load, kPa |
1,75 |
1,75
|