Two - pass vertical fire - tube steam boilers are designed to produce steam with a temperature of no more than 120 ° C (due to the built - in superheater with an overpressure of up to 0.07 MPa (0.7 kg / cm2) in order to supply heat to technological processes in the production of: concrete goods, for steam heating, for steaming chambers, in the construction industry, in the food industry, in the production of corrugated cardboard, in the oil and gas industry, agriculture, for heat treatment of feed, pasteurization of milk, in the utilities, food and woodworking industries.
Specifications
The main parameters and dimensions of two - pass vertical fire - tube steam boilers are shown in the table:
No. | The name of indicators | Brand | ||||||
CRC - 0.3 K. V. | CRC - 0.5 K. V. | CRC - 1.0 K. V. | CRC - 0.3 L. Zh. V. | CRC - 0.5 L. Zh. V. | CRC - 0.3 G. V. | CRC - 0.5 G. V. | ||
1 | View | Stationary, vertical, fire - tube | ||||||
2 | Supply voltage | 50 Hz 220 or 380V * * | ||||||
3 | Steam capacity for normal steam, not less, kg / hour | 300 | 500 | 1000 | 300 | 500 | 300 | 500 |
4 | Steam parameters: | - | ||||||
- working pressure, MPa | 0.02 - 0.06 | |||||||
- permissible excess pressure, no more, MPa | 0.07 | |||||||
- Temperature of superheated steam, no more, ° С | 120 | |||||||
five | Efficiency, not less than% | 78 * | ||||||
6 | Installed power consumption, kW | 1.5 | 1.5 | 2.2 | 1.5 | 1.5 | 1.5 | 1.5 |
7 | Exit to operating mode, min. , No more | 60 | ||||||
eight | Fuel used | assorted coal, firewood, peat briquettes | liquid oven | natural gas | ||||
nine | Fuel consumption kg / hour, no more | 53 | 85 | 128 | 37 | 48 | - | - |
ten | Gas consumption m 3 / hour, no more | - | - | - | - | - | 37 | 48 |
eleven | Safety valve, pcs | 2 | ||||||
12 | Overall dimensions, mm. , No more | without burner | ||||||
- length | 2100 | 2100 | 2700 | 2100 | 2100 | 2100 | 2100 | |
- width | 2300 | 2300 | 2990 | 2300 | 2300 | 2300 | 2300 | |
- height (without chimney) | 2400 | 2800 | 3050 | 2400 | 2800 | 2400 | 2800 | |
13 | Boiler weight, no more, kg | 1270 | 1350 | 2700 | 1270 | 1350 | 1270 | 1350 |
fourteen | The level of mechanization and automation, the technical process of steam production by the boiler, % , (water supply - automatic, fuel loading, slag removal, combustion process control - manually) | 50 | ||||||
fifteen | Service life, years, not less | 6 | ||||||
sixteen | Concentration of harmful substances in the workplace (CO content), mg / m 3 , no more | 20 | ||||||
17 | The noise level at the workplace does not exceed dBA | 76 | ||||||
18 | Availability ratio | 0.99 | ||||||
nineteen | Feed water requirement: | - | ||||||
- suspended matter, mg / l, no more | five | |||||||
- transparency "along the ring", cm | 50 | |||||||
- total hardness, mg. eq / l, no more | five | |||||||
- carbonate hardness, mg eq / l, no more | 3 | |||||||
- iron content, mg / l, no more | 0.1 | |||||||
- oxygen content, mg / l, no more | 0.03 | |||||||
- Н, pH units, no more | eight |
* - provided when burning bituminous coals with a combustion heat of at least 5000 kcal / kg at a moisture content of no more than 12% , ash content no more than 30% .
* * Depending on the boiler configuration
Product structure and delivery set
The collar is supplied to the consumer partially disassembled, complete with assembly spare parts.
The boiler consists of:
- Housing;
- Level sensor;
- Water treatment unit;
- Smoke exhauster;
- Instrument panel;
- Remote Control;
- Chimney sections;
- Spark arrester.
Steam boiler working principle
The technological process of vaporization is as follows:
Flue gases passing through the gas path of the boiler heat up its heat exchange surfaces. Water heated by heat exchange surfaces evaporates. The steam passing through the steam heater is overheated by the exhaust flue gases and enters the consumer. The slags formed during the evaporation of water are periodically removed from the boiler.