- BrandMaipt
- Country of manufactureChina
- Class of power consumptionA+
- Climate classN
- Type of refrigeratorCompressor
- Cooling Capacity90kw to 1650kw
- Running Control ModePLC Full Automatic Control
- Compressor BrandHanbell/Bitzer
- Compressor Type5:6 Asymmetric Semi-Closed Twin Screw
- Chilled Water Flow15.5m3/H to 284m3/H
- Condenser Air Flow21.5m3/H to 627000m3/H
- Optional RefrigerantsR22/R134A/R407c
- Power Supply220V to 575V(Customized)
- Guarantee Period15 Months
- Life-TimeMore Than 5 Years
Energy Saving Industrial Air Cooling System for Industrial Use
BREIF DESCRIPTION
MPSA~ series Air Cooled Screw Chiller is the latest developed product which has a wide cooling capacity range from 90KW to 1650KW, adopt: 5:6 Asymmetric Semi-
closed Twin Screw Compressor, High-efficiency Shell & Tube Dry Type Evaporator, High Efficiency Internal Thread Copper Tube Fin Type Condenser etc. By means of
decades manufacturing experience, we make the whole chiller unit with pretty appearance, reasonable layout and convenient for using &maintenance etc.
The cooling medium could be water, glycol solution or salt solution, supply chilled water through refrigerating cycle for air-conditioning or other industrial equipment.
FEATURES/FUNTIONS/SAFETY PROTECTIONS
FEATURES | * OPTIONAL FUNCTIONS |
- Adopt the well-known brand compressors | * Special brine evaporator |
- Control mode: PLC Full Automatic Control | * RS485 remote control function |
- Copper tube is welded with oxygen free method | * Total heat recovery or part heat recovery |
- 5:6 Asymmetric Semi-closed Screw Compressor | * Customizable painting colour or OEM&ODM |
- SUS integrated pipelines for less pipe resistance | * Complete refrigeration system scheme design |
- Multi-steps energy regulation or stepless regulation | * Explosion-proof electric cabinet or components |
- System pressure & Functional test before shipping | * Customizable power supply and cooling capacity |
- Highly efficient evaporator and condenser (30% energy saving) | * Different refrigerants are available, R22, R134a, R407C etc |
- Electrical devices supplied from OMRON, C8, LG, SCHNEIDER | * Different outlet water Temp.(10°C,7°C,0°C,-5°C to -35°C) is available |
SAFETY PROTECTIONS | |
- Overheating protection of compressor's motor | - Phase protection of power supply |
- Discontinuous flow protection of cooling/chilled water | - Anti-freezing protection of chilled water |
- Over-voltage & under-voltage protection of power supply | - Three-phase Unbalance protection of power supply |
- Protection for exhaust temperature of compressor is too high | - Protection for low pressure of refrigerant is too low |
- Protection for outlet temperature of chilled water is too high | - Protection for high pressure of refrigerant is too high |
TECHNICAL SPECIFICATION
Single Compressor Air Cooled Screw Chiller
Model | MPSA- | |||||||||||
90.1H | 120.1H | 155.1H | 165.1H | 210.1H | 225.1H | 265.1H | 280.1H | 305.1H | 330.1H | |||
Cooling Capacity | KW | 90 | 120 | 155 | 165 | 210 | 225 | 265 | 280 | 305 | 330 | |
104Kcal/h | 8 | 10 | 13 | 14 | 18 | 19 | 23 | 24 | 26 | 28 | ||
Heating Capacity | KW | 98 | 130 | 168 | 179 | 228 | 244 | 288 | 304 | 331 | 358 | |
104Kcal/h | 8 | 11 | 14 | 15 | 20 | 21 | 25 | 26 | 28 | 31 | ||
Running Control Mode | PLC Fully Automatic Control | |||||||||||
Power Supply | 380V/3N ~ 50Hz | |||||||||||
Total Power | KW | 28.6 | 38.1 | 48 | 53.1 | 66.8 | 71.1 | 79.3 | 84.2 | 91.9 | 100.6 | |
Operating Current | A | 50.1 | 66.7 | 84 | 92.9 | 116.9 | 124.4 | 138.8 | 147.4 | 160.8 | 176.1 | |
Compressor | Type | 5:6 Asymmetric Semi-closed Twin Screw Compressor | ||||||||||
Quantity | SET | 1 | ||||||||||
Startup Type | Y-△ Startup | |||||||||||
Energy Regulation | 0 - 33% - 66% - 100% | 0 - 25% - 50% - 75% - 100% | ||||||||||
Refrigerating Power | KW | 26.8 | 35.4 | 44.4 | 48.7 | 60.2 | 64.5 | 72.7 | 76.4 | 84.1 | 91.8 | |
Refrigerating Current | A | 46.9 | 62 | 77.7 | 85.2 | 105.4 | 112.9 | 127.2 | 133.7 | 147.2 | 160.7 | |
Heating Power | KW | 26.1 | 34.5 | 43.3 | 47.5 | 58.7 | 76.9 | 82.4 | 74.5 | 82 | 89.5 | |
Heating Current | A | 45.7 | 60.4 | 75.8 | 83.1 | 102.7 | 134.6 | 144.2 | 130.4 | 143.5 | 156.6 | |
Evaporator | Type | Horizontal Type Shell & Tube Dry Type Heat Exchanger | ||||||||||
Water Flow | m3/h | 15.5 | 20.7 | 26.7 | 28.4 | 36.1 | 38.7 | 45.6 | 48.2 | 52.5 | 56.8 | |
Interface Size | DN65 | DN80 | DN100 | DN125 | ||||||||
Pressure Drop | kPa | 44 | 45 | 47 | 49 | 50 | 50 | 50 | 50 | 52 | 55 | |
Condenser | Type | High Efficiency Internal Thread Copper Tube Fin Type | ||||||||||
Air Flow | m3/h | 34200 | 45600 | 58900 | 62700 | 79800 | 85500 | 100700 | 106400 | 115900 | 125400 | |
Condensing Axial Fan | Quantity | SET | 6 | 6 | 8 | 8 | 6 | 6 | 6 | 6 | 6 | 8 |
Power | KW/set | 0.3 | 0.45 | 0.45 | 0.55 | 1.1 | 1.1 | 1.1 | 1.3 | 1.3 | 1.1 | |
Refrigerant | Type | R22 | ||||||||||
Volume | Kg | 24 | 31 | 41 | 43 | 55 | 59 | 69 | 73 | 80 | 86 | |
Overall Dimensions | Length | mm | 2450 | 2750 | 2950 | 3200 | 3200 | 3200 | 3200 | 3200 | 3550 | 4400 |
Width | mm | 1350 | 1400 | 1400 | 1500 | 2200 | 2200 | 2200 | 2200 | 2200 | 2200 | |
Height | mm | 2020 | 2020 | 2200 | 2200 | 2300 | 2300 | 2300 | 2350 | 2350 | 2350 | |
Weight |
Net Weight | Kg | 1850 | 2000 | 2400 | 2600 | 2800 | 2950 | 3100 | 3300 | 3550 | 3750 |
Running Weight | Kg | 2000 | 2200 | 2600 | 2900 | 3100 | 3180 | 3350 | 3600 | 3900 | 4100 |
Single Compressor Air Cooled Screw Chiller
Model | MPSA- | |||||||||||
360.1H | 420.1H | 450.1H | 490.1H | 530.1H | 550.1H | 635.1H | 695.1H | 740.1H | 825.1H | |||
Cooling Capacity | KW | 360 | 420 | 450 | 490 | 530 | 550 | 635 | 695 | 740 | 825 | |
104Kcal/h | 31 | 36 | 39 | 42 | 46 | 47 | 55 | 60 | 64 | 74 | ||
Heating Capacity | KW | 391 | 456 | 489 | 532 | 576 | 597 | 690 | 755 | 804 | 896 | |
104Kcal/h | 34 | 39 | 42 | 46 | 50 | 51 | 59 | 65 | 69 | 77 | ||
Running Control Mode | PLC Fully Automatic Control | |||||||||||
Power Supply | 380V/3N ~ 50Hz | |||||||||||
Total Power | KW | 112.4 | 130.6 | 140.4 | 153.1 | 166.7 | 171.4 | 198.3 | 218 | 234.1 | 255.7 | |
Operating Current | A | 196.7 | 228.6 | 245.7 | 267.9 | 291.7 | 300 | 347 | 381.5 | 410 | 447 | |
Compressor | Type | 5:6 Asymmetric Semi-closed Twin Screw Compressor | ||||||||||
Quantity | SET | 1 | ||||||||||
Startup Type | Y-△ Startup | |||||||||||
Energy Regulation | 0 - 25% - 50% - 75% - 100% | |||||||||||
Refrigerating Power | KW | 102 | 118.6 | 127.4 | 138.1 | 148.7 | 153.4 | 180.3 | 200 | 212.5 | 234.1 | |
Refrigerating Current | A | 178.5 | 207.6 | 223 | 241.7 | 260.2 | 268.5 | 315.5 | 350 | 372 | 410 | |
Heating Power | KW | 99.5 | 115.6 | 124.2 | 134.6 | 145 | 177.1 | 187.7 | 195 | 207.2 | 228.2 | |
Heating Current | A | 174.1 | 202.3 | 217.4 | 235.6 | 253.8 | 309.9 | 328.5 | 341 | 363 | 399 | |
Evaporator | Type | Horizontal Type Shell & Tube Dry Type Heat Exchanger | ||||||||||
Water Flow | m3/h | 62 | 72.3 | 77.5 | 84.3 | 91.2 | 94.7 | 109.3 | 119.6 | 127.4 | 142 | |
Interface Size | DN125 | DN150 | ||||||||||
Pressure Drop | kPa | 57 | 59 | 63 | 65 | 67 | 69 | 71 | 72 | 74 | 75 | |
Condenser | Type | High Efficiency Internal Thread Copper Tube Fin Type | ||||||||||
Air Flow | m3/h | 136800 | 159600 | 171000 | 186200 | 201400 | 209000 | 241300 | 264100 | 281200 | 313500 | |
Condensing Axial Fan | Quantity | set | 8 | 8 | 10 | 10 | 10 | 10 | 12 | 12 | 12 | 12 |
Power | KW/set | 1.3 | 1.5 | 1.3 | 1.5 | 1.8 | 1.8 | 1.5 | 1.5 | 1.8 | 1.8 | |
Refrigerant | Type | R22 | ||||||||||
Volume | Kg | 94 | 110 | 118 | 128 | 139 | 144 | 166 | 182 | 194 | 216 | |
Overall Dimensions | Length | mm | 4400 | 4600 | 5600 | 5800 | 5800 | 5800 | 7000 | 7000 | 7500 | 7500 |
Width | mm | 2200 | 2200 | 2200 | 2200 | 2200 | 2200 | 2200 | 2200 | 2200 | 2200 | |
Height | mm | 2350 | 2350 | 2500 | 2500 | 2500 | 2500 | 2560 | 2560 | 2560 | 2560 | |
Weight | Net Weight | Kg | 3950 | 4400 | 4600 | 5100 | 5500 | 5650 | 5780 | 5850 | 6000 | 62504300 |
Running Weight | Kg | 4300 | 4800 | 5100 | 5600 | 6100 | 6200 | 6330 | 6400 | 6600 | 6900 |
Double Compressor Air Cooled Screw Chiller
Model | MPSA- | ||||||||||||
180.2H | 240.2H | 310.2H | 330.2H | 420.2H | 450.2H | 530.2H | 560.2H | 610.2H | 660.2H | ||||
Cooling Capacity | KW | 180 | 240 | 310 | 330 | 420 | 450 | 530 | 560 | 610 | 660 | ||
104Kcal/h | 15 | 21 | 27 | 28 | 36 | 39 | 46 | 48 | 52 | 57 | |||
Heating Capacity | KW | 196 | 260 | 336 | 358 | 456 | 488 | 576 | 608 | 662 | 716 | ||
104Kcal/h | 17 | 22 | 29 | 31 | 39 | 42 | 50 | 52 | 57 | 62 | |||
Running Control Mode | PLC Fully Automatic Control | ||||||||||||
Power Supply | 380V/3N ~ 50Hz | ||||||||||||
Total Power | KW | 56.9 | 75.3 | 96.6 | 106.2 | 134.8 | 142 | 158.4 | 170.8 | 183.8 | 201.8 | ||
Operating Current | A | 99.6 | 131.8 | 169.1 | 185.9 | 235.9 | 248.5 | 277.2 | 298.9 | 321.7 | 353.2 | ||
Compressor | Type | 5:6 Asymmetric Semi-closed Twin Screw Compressor | |||||||||||
Quantity | SET | 2 | |||||||||||
Startup Type | Y-△ Startup | ||||||||||||
Energy Regulation | 0-16.5-33-50-66-83.5-100% | 0 - 12.5% - 25% - 37.5% - 50% - 62.5% - 75% - 87.5% - 100% | |||||||||||
Refrigerating Power | KW | 53.6 | 70.8 | 88.8 | 97.4 | 120.4 | 129 | 145.4 | 152.8 | 168.2 | 183.6 | ||
Refrigerating Current | A | 93.8 | 123.9 | 155.4 | 170.5 | 210.7 | 225.8 | 254.5 | 267.4 | 294.4 | 321.3 | ||
Heating Power | KW | 52.2 | 69 | 86.6 | 95 | 117.4 | 123.8 | 134.8 | 149 | 164 | 179 | ||
Heating Current | A | 91.4 | 120.8 | 151.6 | 166.3 | 205.5 | 269.2 | 288.4 | 260.8 | 287 | 313.3 | ||
Evaporator | Type | Horizontal Type Shell & Tube Dry Type Heat Exchanger | |||||||||||
Water Flow | m3/h | 31 | 41.3 | 53.4 | 56.8 | 72.3 | 77.5 | 91.2 | 96.4 | 105 | 113.6 | ||
Interface Size | DN80 | DN100 | DN125 | DN150 | DN200 | ||||||||
Pressure Drop | kPa | 46 | 47 | 49 | 51 | 52 | 52 | 52 | 52 | 54 | 57 | ||
Condenser | Type | High Efficiency Internal Thread Copper Tube Fin Type | |||||||||||
Air Flow | m3/h | 68400 | 91200 | 117800 | 125400 | 159600 | 171000 | 201400 | 212800 | 231800 | 250800 | ||
Condensing Axial Fan | Quantity | set | 6 | 6 | 6 | 8 | 8 | 10 | 10 | 10 | 12 | 14 | |
Power | KW/set | 0.55 | 0.75 | 1.3 | 1.1 | 1.8 | 1.3 | 1.3 | 1.8 | 1.3 | 1.3 | ||
Refrigerant | Type | R22 | |||||||||||
Volume | Kg | 47 | 63 | 81 | 86 | 110 | 118 | 139 | 146 | 160 | 173 | ||
Overall Dimensions | Length | mm | 3800 | 3800 | 4200 | 4400 | 4600 | 5600 | 5600 | 5600 | 6900 | 8000 | |
Width | mm | 2000 | 2000 | 2200 | 2200 | 2200 | 2200 | 2200 | 2200 | 2200 | 2200 | ||
Height | mm | 2300 | 2300 | 2300 | 2300 | 2500 | 2500 | 2500 | 2500 | 2500 | 2500 | ||
Weight | Net Weight | Kg | 3200 | 3330 | 3850 | 4400 | 4800 | 4950 | 5150 | 5450 | 5750 | 5900 | |
Gross Weight | Kg | 3500 | 3700 | 4200 | 4800 | 5300 | 5500 | 5680 | 6000 | 6300 | 6500 |
Double Compressor Air Cooled Screw Chiller
Model | MPSA- | ||||||||||||
720.2H | 840.2H | 900.2H | 980.2H | 1060.2H | 1100.2H | 1270.2H | 1390.2H | 1480.2H | 1650.2H | ||||
Cooling Capacity | KW | 720 | 840 | 900 | 980 | 1060 | 1100 | 1270 | 1390 | 1480 | 1650 | ||
104Kcal/h | 62 | 72 | 77 | 84 | 91 | 95 | 109 | 120 | 127 | 142 | |||
Heating Capacity | KW | 782 | 912 | 978 | 1064 | 1152 | 1194 | 1380 | 1510 | 1608 | 1792 | ||
104Kcal/h | 67 | 78 | 84 | 92 | 99 | 103 | 119 | 130 | 138 | 154 | |||
Running Control Mode | PLC Fully Automatic Control | ||||||||||||
Power Supply | 380V/3N ~ 50Hz | ||||||||||||
Total Power | KW | 229.2 | 266 | 283.6 | 308.6 | 333.4 | 342.8 | 396.6 | 431.2 | 468.2 | 511.4 | ||
Operating Current | A | 401.1 | 465.5 | 496.3 | 540.1 | 583.5 | 599.9 | 694.1 | 754.6 | 819.4 | 895 | ||
Compressor | Type | 5:6 Asymmetric Semi-closed Twin Screw Compressor | |||||||||||
Quantity | SET | 2 | |||||||||||
Startup Type | Y-△ Startup | ||||||||||||
Energy Regulation | 0 - 12.5% - 25% - 37.5% - 50% - 62.5% - 75% - 87.5% - 100% | ||||||||||||
Refrigerating Power | KW | 204 | 237.2 | 254.8 | 276.2 | 297.4 | 306.8 | 360.6 | 400 | 425 | 468.2 | ||
Refrigerating Current | A | 357 | 415.1 | 445.9 | 483.4 | 520.5 | 536.9 | 631.1 | 700 | 743.8 | 819.4 | ||
Heating Power | KW | 199 | 231.2 | 248.4 | 269.2 | 290 | 354.2 | 375.4 | 390 | 414.4 | 456.4 | ||
Heating Current | A | 348.3 | 404.6 | 434.7 | 471.1 | 507.5 | 619.9 | 657 | 682.5 | 725.2 | 798.7 | ||
Evaporator | Type | Horizontal Type Shell & Tube Dry Type Heat Exchanger | |||||||||||
Water Flow | m3/h | 123.9 | 144.6 | 154.9 | 168.7 | 182.4 | 189.3 | 218.6 | 239.2 | 254.7 | 284 | ||
Interface Size | DN200 | DN250 | |||||||||||
Pressure Drop | kPa | 59 | 61 | 65 | 67 | 69 | 71 | 73 | 74 | 76 | 77 | ||
Condenser | Type | High Efficiency Internal Thread Copper Tube Fin Type | |||||||||||
Air Flow | m3/h | 273600 | 319200 | 342000 | 372400 | 402800 | 418000 | 482600 | 528200 | 562400 | 627000 | ||
Condensing Axial Fan | Quantity | set | 14 | 16 | 16 | 18 | 20 | 20 | 20 | 24 | 24 | 24 | |
Power | KW/set | 1.8 | 1.8 | 1.8 | 1.8 | 1.8 | 1.8 | 1.8 | 1.3 | 1.8 | 1.8 | ||
Refrigerant | Type | R22 | |||||||||||
Volume | Kg | 188 | 220 | 235 | 256 | 277 | 288 | 332 | 364 | 387 | 432 | ||
Overall Dimensions | Length | mm | 8000 | 9000 | 9500 | 10200 | 11000 | 11000 | 11800 | 13200 | 13200 | 13200 | |
Width | mm | 2200 | 2200 | 2200 | 2200 | 2200 | 2200 | 2200 | 2200 | 2200 | 2200 | ||
Height | mm | 2500 | 2500 | 2500 | 2500 | 2500 | 2500 | 2560 | 2560 | 2560 | 2560 | ||
Weight | Net Weight | Kg | 6500 | 7400 | 7800 | 8750 | 9200 | 9500 | 9800 | 10500 | 11500 | 12200 | |
Running Weight | Kg | 7200 | 8100 | 8600 | 9600 | 10100 | 10500 | 10800 | 11600 | 12700 | 13400 |
Remark:
Note: 1. Nominal Refrigerating Condition: Chilled water inlet/outlet temperature is 12°C / 7°C, ambient temperature is 35°C;
2. Nominal Heating Condition: Hot water inlet/outlet temperature range is 40°C / 45°C; Ambient dry bulb temperature is 7°C, wet bulb temperature is 6°C;
3. The designed pressure resistance in the water side of evaporator is 1.0MPa. Under nominal conditions, the fouling factor in evaporator side is 0.018m2•°C/KW.
4. Input Power: Allowable fluctuate voltage: ±5%; allowable voltage difference in phase: ±2%. Please notify us if you have special requirements for the outlet water pressure.
Configuration Table for MPSA Series
No. | Name | Brand | Origin | No. | Name | Brand | Origin |
1 | Compressor | HANBELL | TAIWAN | 13 | Expansion Valve (Optional) |
ALCO | USA (For capacity < 700KW) |
BITZER | GERMANY | CAREL | ITALY (For capacity < 700KW) | ||||
3 | AC contactor | LS | SOUTH KOREA | 14 | Pressure Sensor | MAIPT(OEM) | CHINA |
4 | Thermal relay | LS | SOUTH KOREA | 15 | Solenoid Valve | MAIPT(OEM) | CHINA |
5 | AC Transient Protector | MAIPT(OEM) | CHINA | *16 | Check Valve | MAIPT(OEM) | CHINA |
6 | Emergency Stop Switch | SCHNEIDER | FRANCE | *17 | Four-way Valve | MAIPT(OEM) | CHINA |
7 | Evaporator | MAIPT(OEM) | CHINA | 18 | Axial Flow Fan | MAIPT(OEM) | CHINA |
8 | Condenser | MAIPT(OEM) | CHINA | 19 | Electric Cabinet | MAIPT(OEM) | CHINA |
9 | Angle Valve | MAIPT(OEM) | CHINA | 20 | Electric Cable | MAIPT(OEM) | CHINA |
10 | Dry Filter | MAIPT(OEM) | CHINA | 21 | Insulation Material | MAIPT(OEM) | CHINA |
11 | Sight Glass | ALCO | USA | 22 | Water Flow Switch | MAIPT(OEM) | CHINA |
12 | Spray Expansion Valve | MAIPT(OEM) | CHINA | 23 | High/Low Pressure Liquid Reservoir |
MAIPT(OEM) | CHINA |
Remark:
1. Above standard configuration table of air-cooled screw chiller is just for reference, final configuration table is subject to the quotation proposal. 2. Four-way valve and check valve are only equipped for HEAT PUMP unit, but not for single chiller unit.
3. Only choose one between thermal expansion valve and electronic expansion valve.
4. The unit containing the electronic expansion valve won't contain the main solenoid valve.
OPTIONAL ACCESSORIES
Install Accessories for Refrigeration System (optional) | Maintenance Accessories for Chiller Units (optional) | |||||||||
No. | Item Name | Spec. / Model | Unit | Qty | No. | Item Name | Spec. / Model | Unit | Qty | |
1 | Cooling Tower | *To be identified | Nos. | / | 1 | PLC Micro-computer Controller | *To be identified | Nos. | / | |
2 | Chilled Water Pump | *To be identified | Set | / | 2 | Colorful LCD Touch Screen | *To be identified | Nos. | / | |
3 | Cooling Water Pump | *To be identified | Set | / | 3 | Thermal Expansion Valve | *To be identified | Nos. | / | |
4 | Insulation Water Tank | *To be identified | Nos. | / | 4 | Solenoid Valve | *To be identified | Nos. | / | |
5 | Water Running Pump | *To be identified | m | / | 5 | Check Valve | *To be identified | Nos. | / | |
6 | Pipe Reduction | *To be identified | Nos. | / | 6 | Angle Valve | *To be identified | Nos. | / | |
7 | Pressure Gauge | *To be identified | Nos. | / | 7 | Dry Filter | *To be identified | Nos. | / | |
8 | Flexible Joint | *To be identified | Nos. | / | 8 | AC Transient Protector | *To be identified | Nos. | / | |
9 | T-Junction | *To be identified | Nos. | / | 9 | AC Contactor | *To be identified | Nos. | / | |
10 | Elbow | *To be identified | Nos. | / | 10 | Thermal Relay | *To be identified | Nos. | / | |
11 | Butterfly Valve | *To be identified | Nos. | / | 11 | High/Low Pressure Gauge | *To be identified | Nos. | / | |
12 | Check Valve | *To be identified | Nos. | / | 12 | High/Low Pressure Switch | *To be identified | Nos. | / | |
13 | Flanges | *To be identified | Nos. | / | 13 | Liquid Sight Glass | *To be identified | Nos. | / | |
14 | Y-Strainer | *To be identified | Nos. | / | 14 | Water Flow Switch | *To be identified | Nos. | / |
Note: | a. All above accessories list is just for a reference, different projects or using conditions may have differences, please contact us for confirmation. | |||||||||
b. Both the INSTALL and SPARE Accessories listed above could be added or deleted according to buyer's actual requirements. |
WHY CHOOSE MAIPT
>> You want experience… |
Experienced R&D team bring more than 10 years of process cooling & heating experience with knowledgeable application, product and service specialists available to discuss your needs. |
>> You want someone who understands your process... |
Provided with experience in a wide range of process cooling & heating industries. When you give us the chance, we will show the rich experience and get you the correct solution to your problems. |
>> You want a product that fits your unique needs... |
Offer a wide range of standard units, what's more, our application specialists can suggest the customized units to meet unique needs. |
>> You want specialized control... |
Build our own system controls from tailor made embedded micro-processor base products to PLC options. System control makes the difference in your process repeatability, efficiency and reliability. |
>> You want professional design manufacturer… |
MAIPT specialize in industrial fluid process temperature control fields, and provide the complete systems solutions. |
>> You want energy efficient solutions... |
Our specialists are aware of the rising cost of energy and the pressure to reduce energy consumption and we offer many energy saving products that favor lifetime costs. |
>> Our Service: |
OEM & ODM, or any other unique customized demands are acceptable. |
Any price inquiries or technical inquiries will be responded within 24 hours. |
Experienced technical engineers will give the model selection guide or help design the customized model. |
Detailed quotation scheme and system configuration will be provided to the customer together. |
The whole order process is tracked throughout, |
order production → performance test → packaging → transportation → customs declaration → shipment |
customer will receive the notification mail (include photos, report or other documents) in each process. |
Besides the temperature control units, other install parts or auxiliary equipments is optional according to customers' requirements. |
All necessary installation documentation (e.g. Electrical diagram, User Manual) will be provided in both electronic copy and hard copy. |
Perfect after-sales service system, it's including: |
Technical guidance, detailed machine maintenance methods, troubleshooting solutions, regular return visit etc. |
>> Our Warranty |
All the products are passed strict test, and MAIPT provide 15 months guarantee since the date of bill of lading. During this guarantee period, MAIPT provide spare parts without any charge in case of quality discrepancy caused by us. If out of guarantee period, we still can charge the buyer cost price of spare parts and provide Technical Product support for customers. |