Currency EUR
Cable with polyvinylchloride isolation for electrical units of Kuvvng (A)-LS on TU 16-705.502-2011 (it is made according to the license of JSC VNIIKP) – Shchuchinskij zavod Avtoprovod, OAO | all.biz
ALL.BIZ Products Electrical Equipment Electrical cables, wires and cords Various applications cables PVC cables Cable with polyvinylchloride isolation for electrical units of Kuvvng (A)-LS on TU 16-705.502-2011 (it is made according to the license of JSC VNIIKP)
Buy Cable with polyvinylchloride isolation for electrical units of Kuvvng (A)-LS on TU 16-705.502-2011 (it is made according to the license of JSC VNIIKP)
Cable with polyvinylchloride isolation for electrical units of Kuvvng (A)-LS on TU 16-705.502-2011 (it is made according to the license of JSC VNIIKP)

Cable with polyvinylchloride isolation for electrical units of Kuvvng (A)-LS on TU 16-705.502-2011 (it is made according to the license of JSC VNIIKP)

Products from producer
In stock
Reconfirm the price with seller
Payment:
Shipping:
Seller
Belarus, Schuchin
(View map)
+375 
Display phones
Technical characteristics
  • BrandЩучинский завод Автопровод, ОАО
  • Country of manufactureBelarus
  • Outside diameterв ассортименте "
  • Conductor materialCopper
  • Minimum bend radiusв ассортименте "
Description
Appointment

Wires are applied to electrical units at stationary laying in lighting and power networks, and also to installation of electric equipment, cars, mechanisms and machines, internal electroinstallations on a rated alternating voltage to 450/750 B inclusive with a nominal frequency up to 400 Hz or constant tension to 1000 V inclusive to wires and on a rated alternating voltage to 300/500 B inclusive with a nominal frequency up to 400 Hz to cables.

Type of a climatic modification on TU 16-705.501-2010-UHL2 in accordance with GOST 15150.

Type of a climatic modification on TU 16-705.502-2011-U in accordance with GOST 15150.

PUV - a wire single-core, with a copper vein, with PVC isolation, without cover;

PUGV - a wire single-core, with a flexible copper vein, with PVC isolation, without cover.

KUVV - a cable with copper veins, with isolation and a cover from polyvinylchloride plastic compound

KUGVV - a cable with copper flexible veins, with isolation and a cover from polyvinylchloride plastic compound.

DESIGN

CONDUCTING VEIN - copper single-wire

ISOLATION - PVC plastic compound. For wires and a cable with an index ng (A)-LS-PVH plastic compound of the lowered fire danger. The isolated veins have a distinctive coloring.

OBOLOCHKA-Puvvng (A)-LS, PUGVVNG (A)-LS-PVH plastic compound of the lowered fire danger.

The NUMBER of VEINS - 1; PUVV one - two - and three-vein; KUVV, KUGVV-dvukh-, three - four - and five-vein.

SECTION of VEINS, mm ²: 0,50; 0,75; 1,0; 1,5; 2,5; 4; 6; 10; 16; 25; 35; 50; 70; 95; 120, 150,185.

TECHNICAL CHARACTERISTICS

The electric resistance of isolation of a cable counted for 1 km of length and temperature of 20 °C has to be not less than 5 Megohms.

Wires are resistant to influence of mechanical blows, linear acceleration, bends, vibration loadings, acoustic noise, mold mushrooms.

Wires do not extend burning at single laying.

Radius of a bend of wires at installation has to be not less than 10 nominal diameters for wires of the PUV, PUVV brand and the KUVV cable and not less than 5 nominal outer diameters for wires of the PUGV brands, PUGVV and a cable of brand of KUGVV. Bend radius for flat wires has to be not less than 10 nominal external sizes on a smaller axis.

It is long the admissible temperature of heating of veins - no more than +70 °C.

Construction length of wires - not less than 100 m, is allowed delivery by lengths not less than 20 m in number of no more than 20% of party.

Average service life of wires - not less than 20 years at observance by the consumer of conditions of transportation, storage, installation and operation. A warranty period of operation - 5 years

Instructions on operation:

- wires are intended for laying in steel pipes, boxes, on trays, etc., for installation of electric chains

- wires are intended for operation at ambient temperature from minus 50 °C to 65 °C and relative humidity to 98%.

- it is long the admissible temperature of heating of veins at operation not has to exceed 70 °C.

The wire of PUV is analog of a wire of PV1 in accordance with GOST 6323

The wire of PUGV is analog of a wire of PV4 in accordance with GOST 6323

Comments about the company  Shchuchinskij zavod Avtoprovod, OAO
100%
of positive feedback from the 2
50% of responses during the day
50% of transactions executed in time
100% of actual goods description
This means that 100% of buyers found cooperation with this company successful and recommend this seller
all (2) positive (2) negative (0)
Good
Anonymous
02.05.2018
Allbizconfirms appeals
Allbiz confirms a receiver's contacting via resource
Prompt response: Within one hour
Was the order is executed in time: Yes
Corresponding of goods/services description: Yes
Good
Anonymous
27.11.2017
Allbizconfirms appeals
Allbiz confirms a receiver's contacting via resource
Цена нас устроила. Но если учитывать транспортные расходы, то мы взяли из Минска попутным транспортом и нам оказалось это более выгодно
Prompt response: A few days later
Was the order is executed in time: I can not appreciate
Corresponding of goods/services description: Yes
Contact the seller
Cable with polyvinylchloride isolation for electrical units of Kuvvng (A)-LS on TU 16-705.502-2011 (it is made according to the license of JSC VNIIKP)
Cable with polyvinylchloride isolation for electrical units of Kuvvng (A)-LS on TU 16-705.502-2011 (it is made according to the license of JSC VNIIKP)
Shipping method
Payment method
Compare0
ClearSelected items: 0